ABB Robot Servo Motor Replacement: Check the Cable First

Time: 2026-11-20 Hits: 0

An IRC5 that reports a motor current fault on one axis does not tell you whether the motor, the power cable or the drive unit is at fault. ABB's own troubleshooting manual resolves that ambiguity by asking you to measure the cable and the motor separately, with the connections broken. Skip that step and the servo motor replacement goes in, the same event comes back, and the axis is still down.

If you already have the event log open, the numbers below tell you which of the three parts to test first. If you are holding a motor that has just come off the robot and want to know whether the cable caused the failure, go straight to the measurement section and the part number table at the end. Send us the event number, the motor nameplate and a photo of the cable label and we will confirm which article your machine needs before you order.

The drive, the cable and the motor are one circuit, not three parts

On an IRC5 the axis drive does not see the motor directly. It sees the motor through the power cable, and it sees the rotor position through a second path that runs from the motor's resolver, through the signal cable, to the serial measurement board on the manipulator and on to the axis computer.

That layout produces a predictable failure pattern. A damaged power cable and a failing motor produce the same current event, because both change the resistance and inductance the drive is measuring. A damaged signal cable and a failing measurement board produce the same position event, for the same reason. The controller cannot tell you which one it is. It can only tell you which quantity went out of range.

This is why the event number is a starting point and not a diagnosis. It narrows the candidate list to two or three parts. The meter decides between them.

Read the event number before you take anything apart

The IRC5 event log groups these faults by the quantity that went out of range, and that grouping is what points at the part. The table below uses event numbers and wording from ABB's Operator's manual - IRC5 Troubleshooting, document 3HAC020738-010, revision J.

Event What the manual says went out of range Parts that can cause it
34203, 34303, 34304 Motor current too high for the joint; excessive torque current deviation Motor, power cable, motor data in configuration, DC bus or supply voltage
38101, 38103 Transmission fault or interruption between axis computer and serial measurement board Signal cable and its shield, serial measurement board, axis computer
39466 Motor current above the permitted range Mechanical load, stalled motor, collision, additional axis sizing
20252 to 20258 Motor temperature too high on DRV1 to DRV4 Cooling, blocked air filter
37098, 37101 Brake circuit open, or brake unable to engage Brake circuit, brake relay, motor brake

Read the table down the middle column, not across. The current events point at a short list that includes the cable. The SMB events point at a short list that includes the cable. The temperature and brake events do not point at the cable at all, and treating them as cable faults wastes a shift.

34203 and 34303: the manual asks for two measurements, not one

The recommended actions for event 34203 include a step that is easy to read past: measure the motor cable and the motor separately, with the connection broken, by measuring their resistance. Event 34303 lists a badly connected or damaged motor cable and a short between motor cable phases or to ground among its possible causes, and asks you to verify that the cable is undamaged and correctly connected before replacing anything.

That is the manual telling you the cable is a suspect in its own right, not an accessory to the motor. A motor that has lost a winding and a cable with a chafed conductor both raise the current the drive reports, and both leave the same event in the log.

Splitting cable from motor with a meter

Do the electrical checks with the robot isolated and locked out, the axis supported, and the motor cable disconnected at both ends, so neither the drive nor the motor is in the measurement. The two ends are named in the product manual: R1.MP on the manipulator, and XS1 in an IRC5 cabinet or X1 in an OmniCore cabinet.

Across the power conductors. Measure resistance phase to phase on the cable, then on the motor terminals. A cable with a phase to phase short reads far below the motor winding resistance. A cable with an open conductor reads open on one pair and normal on the others. Compare the three readings against each other: a cable that is healthy reads consistently across all three pairs.

From each conductor to ground. Measure insulation resistance from each power conductor to the cable shield and to the machine frame. A reading that collapses toward zero points at a conductor rubbed through inside the jacket, which is what a cable that has been flexing at a clamp or a cover edge for years looks like from the inside.

Motor windings against each other. With the cable out of the circuit, measure the motor windings phase to phase. A winding set that is balanced reads consistently; one that is shorted or open stands out against the other two. This is the measurement that separates "the cable is bad" from "the motor is bad" when the drive event is identical.

The cable while it moves. A conductor that is broken inside intact insulation reads normal at rest. Bend the cable through the range it sees in production, at the wrist and at the base entry, and watch the reading. A value that jumps while the cable is flexed is a broken conductor, and it explains an event that appears only on certain moves.

The manual does not publish a pass or fail resistance for your motor, and this article will not invent one. The three phase readings against each other, and the reading against the nameplate data for that motor, are what you compare. If you do not have the winding data for the motor on your machine, send us the nameplate and we will tell you what the number on it refers to.

If the readings have already pointed at the cable, the two that cover the run from the cabinet to the manipulator are the 15 m power cable and the 15 m shielded pair. The shorter mounting takes a different article, the 7 m shielded pair, because length changes the part number.

38101 and 20455: when the fault looks like the board but sits in the cable

Event 38101 is a transmission fault between the axis computer and the serial measurement board. Its possible causes, in the order the manual gives them, are poor contact or damaged cable screening, particularly where a non-ABB additional axis cable is used, followed by a fault in the serial measurement board or the axis computer.

That ordering matters when you are deciding what to buy. Its recommended actions include confirming that the cable between the board and the axis computer is connected to ABB specification, confirming the shield is connected at both ends, and confirming there is no severe electromagnetic interference near the robot wiring. A signal cable with a shield that has come loose at one end, or a pin pushed back in the connector shell after repeated mating, produces exactly the position and synchronisation events that a failing board produces. Event 20455 goes further and reports an incorrect position value from the serial measurement board, and its recommended actions are to check the resolver and the resolver connection before replacing the board or the resolver.

A cable that has been disturbed during nearby work is a common source here. If the axis was fine before a motor or gearbox was changed and reports a position fault afterwards, check that both connector ends are fully seated and that the shield is still landed before you order a board.

39466 and the motor temperature events are not cable faults

Event 39466 reports motor current above the permitted range, and the manual's possible cause is a motor load that is too high or a motor that has stalled, possibly after a collision. The recommended actions are to check for a collision, reduce the speed in the user program, and check the load on an additional axis against what the drive unit can carry. Nothing in that list is electrical, and nothing in it points at the cable.

The motor temperature events, 20252 to 20258 for DRV1 to DRV4, report that the motor temperature is too high and ask you to let the motor cool before enabling power again, and to check the air filter option for blockage. A robot that reports temperature events after long high duty cycles is telling you the cooling path needs attention, not that a part has failed. Replacing a motor or a cable will not change it.

Both groups are worth recognising for a practical reason: they are the two cases where a replacement part does not fix the fault, and where the axis keeps stopping after the new part is fitted.

A brake fault is not a motor fault

Event 37098 reports that the brake monitoring on the manipulator control board detected an open circuit on an axis and opened all brakes. Event 37101 reports that the brake on a mechanical unit cannot engage, with the robot at risk of dropping when power is removed. The recommended checks are on the brake circuit and the brake relay, including any external brake relay defined in the configuration.

A brake that will not release, or a brake that will not hold, is often read as a failed motor because the brake is built into the motor on most ABB axes. The distinction shows up in the symptom: a brake that holds but will not release stalls the axis at the first commanded move, while a winding fault shows up as a current event as soon as the drive enables. Get the symptom right before you price the part.

After the swap: the work that is not in the box

Fitting the motor is the short part of the job. The IRC5 will not let you run production until the revolution counters are updated, and events 10036 and 20032 are what the controller raises when they are not.

The sequence that keeps a motor change from turning into a second breakdown:

  1. Isolate and lock out all supplies, and support the axis before unbolting anything.
  2. Record the motor label, the connector positions and the cable routing before removal, including any tie points that hold the cable at its bend radius. ABB gives the minimum bending radius for static floor cables as 10 times the cable diameter (3HAC033453-001, page 105), which is the figure to hold when the replacement is tied back into the same route.
  3. Fit the replacement with the same sealing and mounting parts. The sealing parts listed for the job are there for a reason: a missing O-ring at the motor flange is an ingress path into the motor.
  4. Recover the axis reference and update the revolution counters following the procedure for your robot model and RobotWare version.
  5. Verify brake action with the axis unloaded, then jog at low speed and confirm direction before running a cycle.
  6. Run one complete cycle in manual before returning the cell to automatic.

If the replacement motor is a used original, confirm the condition with us before ordering and check the brake and the resolver on the unit before it goes on the robot. A used motor with a good winding and a weak brake will pass the electrical check and fail on the first power down.

ABB servo motor replacement: part numbers to have in hand before you call

The 3HAC prefix is shared by motors, cables and drive units, so the prefix alone does not tell you which of the three you are holding. What identifies the article is the label on the failed unit, the robot model and the axis position, and that is the information to collect before you ask for a price.

Article type Example part numbers What to read off the failed unit
AC servo motor, axis specific 3HAC057431-001, 3HAC034164-002, 3HAC034165-002, 3HAC054560-001 Motor nameplate article number, robot model, axis number
Power cable, cabinet to manipulator 3HAC026787-001 (7 m), 3HAC026787-002 (15 m), 3HAC026787-003 (22 m), 3HAC026787-004 (30 m) Part number printed on the cable label, the length, both connector ends
Shielded cable to the SMB 3HAC2530-1 (15 m), 3HAC2493-1 (7 m), 3HAC4050-1 (SMB signal cable) Cable label, length, connector shell condition
Drive unit in the cabinet 3HAC025338-004 Drive unit label, cabinet type, drive system

Those four lengths are not a decoded numbering rule. They are the articles ABB lists in the product manual for the robots that ship with them: 3HAC033453-001 revision AG, page 105, for IRB 4600, and 3HAC044266-001 revision AL, page 108, for IRB 6700. The same four numbers appear in both manuals, so a 15 m cable is the standard power cable on either robot.

Two of these are worth a note. The shielded cable part number changes with length and with robot family, so the same physical cable in a different length is a different article, and matching on the robot model alone is not enough. On IRB 4600 and IRB 6700 the signal cable is a different family again, 3HAC068917-001 for 7 m through 3HAC068920-001 for 30 m, so the model decides the family and the length decides the suffix. The motor number changes with the axis position on the same robot, so a motor that fits axis 2 of one model is not interchangeable with axis 3 of the same model.

If you are stocking for more than one robot, start with the cabinet to manipulator run and the shielded pair. Both flex on every cycle and both are cheaper to hold than a motor. A cable on the shelf is the difference between waiting for a delivery and finishing the job.

If the measurement already told you which part failed

A cable that reads open on one phase, or shorted to ground, is a cable order. A motor whose windings read unbalanced with the cable out of circuit is a motor order. The articles below are the ones this article keeps pointing at, and each page carries the article number, the condition options and the fit notes for the robot family it covers.

If the length or the robot family you need is not on those pages, the ABB cables and dress packages and ABB drive units and servo motors catalogue pages carry the current range by robot type.

What to send us

For a quote we need the article number from the failed unit, the robot model and serial number, and the axis position. A photo of the motor nameplate and the cable label is enough if the number is unreadable, and the serial number alone is enough for us to start. We reply within 24 hours, and the first reply is a confirmation of which article your machine needs, not a price list.

If you are not sure whether the fault is the motor, the cable or the drive unit, send the event number and the measurements you have. We will tell you which one to test next, and if the answer is that you do not need a part from us, we will say so.

One email with the article number and the robot serial is enough to start. You get a fit confirmation before any price.

Request a Quote

FAQ

How do I tell whether the motor or the cable is faulty?

Disconnect the cable at both ends, then measure the cable and the motor separately. Compare the three phase to phase readings on each, and measure insulation resistance from each conductor to ground. A cable with one conductor open or one pair shorted reads differently from a balanced motor winding. ABB's troubleshooting manual asks for exactly this split measurement for current events such as 34203.

Can I replace the motor without replacing the cable?

Yes, and in most cases you should. Replace the cable when the measurement points at it, when the connector shell is cracked or a pin is pushed back, or when the jacket is damaged at a clamp or a bend. Replacing both when only one has failed adds cost without removing a fault.

What happens to the revolution counters after a motor change?

They have to be updated before the controller will let the axis run. Events 10036 and 20032 block motion until the counters are updated, and the procedure depends on the robot model and the RobotWare version. Follow the procedure for your build rather than a generic sequence.

Does the same event number always mean the same failed part?

No. Events 34203 and 34303 both include the motor and the power cable among their possible causes. The event tells you which quantity went out of range, not which component caused it. The measurement is what separates them.

Can I use a non-ABB cable?

ABB's manual notes that poor contact or damaged screening is a cause of SMB communication faults, particularly where a non-ABB additional axis cable is used. If a non-original cable is already fitted, check the shield landing and the connector condition first, and match the replacement to the specification for your robot rather than to the old cable alone.

Is a used original motor acceptable for a production robot?

It can be, provided the condition is confirmed before purchase and the brake and resolver are checked on the unit. Ask for the condition to be stated in writing and confirm what happens if the unit fails the check on arrival. A used motor is a reasonable choice for a spare; for the axis that carries the highest duty cycle, a new original is the safer purchase.

What information do I need to send for a quote?

The robot model and serial number are enough to start, even when the article number on the failed unit is unreadable. Add the axis position and a photo of the nameplate or the cable label and we can usually confirm the article in the first reply.

Can I ask a technical question without buying anything?

Yes. Send the event number, the robot model and what you have measured so far. If the fault is mechanical, a configuration error or a cooling problem, we will tell you that instead of quoting a part.

References

  1. ABB, Operator's manual - IRC5 Troubleshooting, document 3HAC020738-010, revision J (RobotWare 5.13). Event entries 34203, 34303, 34304, 38101, 38103, 39466, 20252 to 20258, 37098, 37101, 10036, 20032, 20455.
  2. ABB, Product manual - IRB 4600, document 3HAC033453-001, revision AG, section 2.8.1 Robot cabling and connection points, page 105. Power cable lengths, connection points R1.MP to XS1 or X1, and the 10 times diameter bending radius for static floor cables.
  3. ABB, Product manual - IRB 6700, document 3HAC044266-001, revision AL, section 2.6.1 Robot cabling and connection points, pages 107 and 108. The same four power cable articles and the signal cable family 3HAC068917-001 to 3HAC068920-001.
  4. ABB, Product manual - IRC5, document 3HAC021313-001, cited as a reference document in 3HAC020738-010.
  5. ABB, Operator's manual - IRC5 with FlexPendant, document 3HAC16590-10, cited as a reference document in 3HAC020738-010.

About this article. Written and maintained by the SongWei Robotics spare parts team in Shanghai. Last updated 20 November 2026. Technical content checked against the ABB manual revisions named above. Event numbers and recommended actions are quoted from 3HAC020738-010; cable articles and dimensions are quoted from the two product manuals. The manual revision that ships with your RobotWare governs your machine. SongWei Robotics is an independent supplier of industrial robot spare parts and is not affiliated with ABB. Robot models, part numbers and event numbers are the property of their respective owners.